Programming languages per IEC 61131-3: Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD), Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
Programming environment: WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Indicators: LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS/BT, NS) red/green: Status of node/BACnet, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: Status of system power supply, field supply
Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Input current (typ.) at nominal load (24 V): 500 mA
Power supply efficiency (typ.) at nominal load (24 V): 90 %
Power consumption (5 V system supply): 440 mA
Total current (system supply): 1700 mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
Current carrying capacity (power jumper contacts): 10 A
Number of outgoing power jumper contacts: 3
Isolation: 500 V system/field
Connection Data
Connection technology: communication/fieldbus: BACnet/IP: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45
Connection technology: system supply: 2 x CAGE CLAMP®
Connection technology: field supply: 6 x CAGE CLAMP®