UL International Netherlands B.V., UL, E175199 Sec.6, UL 508
Specifications
Notes
Note: To prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing may reduce service life.
Control Circuit
Nominal input voltage UN: AC 24 V
Input voltage range: -20 … +10 %
Nominal input current at UN: 50 mA
Load Circuit
Number of changeover/switchover contacts: 4
Contact material (relay): AgCe + Au
Limiting continuous current: 5 A
Inrush current (resistive) (max.): (AC) 15 A / 4 s
Switching voltage (max.): AC 250 V
Switching power (resistive) (max.): AC 1250 VA; DC (see load limit curve)
Switching capacity: AC-15: 1 A / AC 240 V; DC-13: 2 A / DC 24 V
Recommended minimum load: 5 V / 1 mA / 50 mW
Pull-in time (typ.): 25 ms
Drop-out time (typ.): 35 ms
Bounce time (typ.): 4 ms
Electrical life (NO; resistive load; 23 °C): 100 x 103 switching operations