On-Line Electronics will be closed for the Holidays from Tuesday, December 24th, 2024 through Wednesday, January 1, 2025. There will be no shipping or receiving during this time. We will be open for business on Thursday January 2, 2025. From our families to yours, HAPPY HOLIDAYS!
Protection: Reverse voltage protection for ULS + Uo; Short circuit protection for sensor supply
Supply voltage (system and sensor): 24 VDC(-25 … +30 %); Logic and sensors (ULS)
Power consumption (system and sensor): 40 mA
Power consumption, system and sensor (note): + sensors (max. 400 mA)
Supply voltage (field): 24 VDC (-25 … +30 %); Actuators (UA), for transmission only
Power consumption, field supply (module with no external load): 5 mA
Isolation: 500 V supply/system bus
Indicators: LED (F) red: Error status; LED (SB) green/red/orange: System bus status; LED (ULS, UA) green: Power supply status; LED (0 … 7) yellow: Status/diagnostics DI 1 … DI 8; Non-retentive displays
Current carrying capacity (supply connections): 8 A
Connection of 2-wire BEROs: Admissible closed current: 1.5 mA (max.)
Connection Data
Connection technology: inputs/outputs: 4 x M12 socket; A-coded; 4-pole
Connection technology: field supply: 1 x M12 plug; 4-pole; A-coded; 1 x M12 socket, 4-pole, A-coded
Connection technology: system supply: 1 x M12 socket; 4-pole; A-coded; 1 x M12 plug; 4-pole; A-coded
Connection technology: system bus: 1 x M12 socket, 5-pole, B-coded, shielded; 1 x M12 plug, 5-pole, B-coded, shielded
Connection requirement, permissible cable length: 30 m
Connection requirement (permissible cable type): Digital inputs: unshielded