UL International Germany GmbH, UL, E175199 Sec.5, UL 508
Specifications
Technical Data
Number of analog inputs: 4
Total number of channels (module): 4
Signal type: Current || Voltage
Signal type (current): 0 … 20 mADC; 4 … 20 mADC
Voltage signal type: 0 … 10 VDC; -10 … +10 VDC
Signal type (configurable): Yes
Sensor connection: 4 x (2-wire, 3-wire, 4-wire); External shield via knurled nut
Signal characteristic: Differential
Resolution [bit]: 16 bits
Input resistance (max.): 200 Ω
Process data width: 8-byte data + status
Parameterizable functions: I/O diagnostics (per module): Short circuit/overload (encoder supply); Undervoltage (ULS + UA) || I/O diagnostics (per channel): Measurement range overflow/underflow or wire break at 4 … 20 mA; Overcurrent; Limit value violation (min./max.) || Online simulation (per module): Diagnostics || Online simulation (per channel): Lock/Unlock; Simulation value: according to measurement range; Diagnostics || Measurement range (per channel): Parameterizable || Input filter (per channel): 50 Hz/ 60 Hz/ Filter "Off" || Limiting values (per channel): Min./Max. || Substitute value (per channel): Value
Protection: Reverse voltage protection for ULS + Uo; Short circuit protection for sensor supply
Internal resistance: 100 kΩ
Measurement error (reference temperature): 25 °C
Measurement error – deviation (max.) from the upper-range value: 0.2 %
Temperature coefficient: ≤ 100 ppm/K of measurement range
Sampling delay (channel/channel): 100 µs
Sampling delay (module): 1 ms
Sampling repetition time: 1 ms
Supply voltage (system and sensor): 24 VDC(-25 … +30 %); Logic and sensors (ULS)
Power consumption (system and sensor): 50 mA
Power consumption, system and sensor (note): + sensors (max. 400 mA)
Supply voltage (field): 24 VDC (-25 … +30 %); Actuators (UA), for transmission only
Power consumption, field supply (module with no external load): 5 mA
Isolation: 500 V supply/system bus
Indicators: LED (F) red: Error status; LED (SB) green/red/orange: System bus status; LED (ULS, UA) green: Power supply status; LED (Ch1 … Ch4) yellow: Status AI 1 … AI 4; LED (Er1 … Er4) red: Error AI 1 … AI 4; Non-retentive displays
Current carrying capacity (supply connections): 8 A
Monotonicity without error codes: Yes
Conversion method (2): SAR
Conversion time (2): 1 ms
Maximum error over the full temperature range: ≤ ±0.6 % of the measurement range
Voltage-proof: Up to 32 V (internal current limitation)
Connection Data
Connection technology: inputs/outputs: 4 x M12 socket; A-coded; 5-pole
Connection technology: field supply: 1 x M12 plug; 4-pole; A-coded; 1 x M12 socket, 4-pole, A-coded
Connection technology: system supply: 1 x M12 socket; 4-pole; A-coded; 1 x M12 plug; 4-pole; A-coded
Connection technology: system bus: 1 x M12 socket, 5-pole, B-coded, shielded; 1 x M12 plug, 5-pole, B-coded, shielded
Connection requirement, permissible cable length: 30 m
Connection requirement (permissible cable type): Analog inputs: unshielded