UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
TUEV Nord Cert GmbH, IECEx, IECEx_TUN_14.0035_X, IEC 60079-0
Specifications
Technical Data
Number of measurement inputs: 6 (3 voltage measurement inputs*, 3 current measurement inputs*) *Only 2 voltage/current measurement inputs can be used for DC measurement!
Signal type: Power measurement
Signal form: Any periodic signals (considering the threshold frequencies)
Resolution [bit]: 24 bits
Data width: 2 x 128-bit data; 2 x 64-bit control/status
Voltage path input resistance (typ.): 1072 kΩ
Current path input resistance (typ.): 15 kΩ
Reference for measurement error: AC current/voltage
Measurement error (reference temperature): 25 °C
Measurement error – deviation (max.) from the upper-range value: 0.5 %
Reference for measurement error (2): AC current/voltage; DC measurement (2 channels only)
Measurement error, reference temperature (2): 25 °C
Measurement error, deviation (max.) of the upper-range value (2): 1 %
Measurement current (max.): 1 … 20,000 A via ext. shunts (DIN 43703, DIN EN 60051 (50 … 300 mV))
Measurement cycle time: Adjustable for arithmetic mean value, Min_Max_Values
Frequency range (mains frequency): 45 … 65 Hz
Frequency range (harmonics analysis): 0 … 3300 Hz
Limit frequency: 15.9 kHz
Rated voltage: VLN = 277 V AC/DC; VLL = 480 V AC
Calculated values: Line-to-line voltage, power output, energy, power factors, mains frequency, harmonic analysis (up to the 41st harmonic), THD
Measurement method: True RMS measurement
Supply voltage (system): 5 VDC; via data contacts
Power consumption (5 V system supply): 100 mA
Isolation: 4 kV system/field
Connection Data
Connection technology: inputs/outputs: 8 x CAGE CLAMP®