UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA00000Y7
CQST/CNEx, CCCEx, 2020312310000214, CNCA-C23-01
National Radio Research Agency, KC, MSIP-REM-W43-AOM750, Article 58-2, Clause 3
Specifications
Technical Data
Number of analog outputs: 2
Total number of channels (module): 2
Signal type: Current || Voltage
Signal type (current): 0 … 20 mADC; 4 … 20 mADC
Voltage signal type: 6 … 18 VDC
Signal type (configurable): Yes
Actuator connection: 2 x (2-wire, 4-wire)
Resolution [bit]: 16 bits
Data width: 2 x 16-bit data; 2 x 8-bit control/status (optional)
Load impedance (voltage output): ≥ 1.8 kΩ
Load impedance (current output): ≤ 500 Ω
Conversion time (typ.): 5 ms
Output error, reference temperature: 25 °C
Output error, deviation (max.) of the upper-range value: 0.05 %
Temperature coefficient: < ±100 ppm
Recovery time (typ.): 0.3 ms
Supply voltage (system): 5 VDC; via data contacts
Power consumption (5 V system supply): 95 mA
Supply voltage (field): 24 VDC (-15 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed!
Dielectric strength: 510 VAC/775 VDC; per EN 60870-2-1
Rated surge voltage: 1 kV
Number of incoming power jumper contacts: 2
Number of outgoing power jumper contacts: 2
Current carrying capacity (power jumper contacts): 10 A
Derating: Derating (supply voltage): Surrounding air temperatures under laboratory conditions: (-25 … +30 %); for −40 … +55 °C: 24 V (min. … +20 %); for +55 … +70 °C: 24 V (min. … +10 %); Voltage range (min.): 21,6 V; Current range (min.): 20,4 V; Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
Connection Data
Connection technology: inputs/outputs: 8 x CAGE CLAMP®
Relative humidity (with condensation): Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance: Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance: Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference: Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference: Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %: 10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %: 25 ppm
Commercial Data
Packaging type: Box
Country of origin Sales Organisation Germany: DE
GTIN: 4050821460367
Customs tariff number Sales Organisation Germany: 85389099990