Underwriters Laboratories Inc., UL, E198726 Sec.1, UL 121201
UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
National Radio Research Agency, KC, MSIP-REM-W43-SIM750
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA00000Y7
TUEV Nord Cert GmbH, IECEx, IECEx TUN 16.0046X, IEC 60079-0
American Bureau of Shipping, ABS, 18-HG1778162-PDA
CQST/CNEx, CCCEx, 2020312310000214, CNCA-C23-01
Specifications
Technical Data
Signal type: RS-232 || RS-422 / RS-485
Baud rate: 300 Baud … 115.2 kBd
Bit transfer: RS-485/-422: ISO 8482 / DIN 66259 - 4; RS-232: EIA/TIA-232-F
Transmission channels: 1 TxD / 1 RxD, full duplex, half duplex, 7- or 8-bit data, 1 or 2 stop bits
Line length: RS-485/-422: max. approx. 1000 m, RS-232: max. 40 m, data exchange mode/DMX: max. 100 m twisted-pair cable
Data width: 8, 24 or 48 bytes (parameterizable)
Number of data bits: 7/8, adjustable
Number of stop bits: 1/2, adjustable
Buffer: 2560 bytes for reception / 512 bytes for transmission
Supply voltage (system): 5 VDC; via data contacts
Power consumption (5 V system supply): 85 mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed!
Rated surge voltage: 1 kV
Number of incoming power jumper contacts: 2
Number of outgoing power jumper contacts: 2
Current carrying capacity (power jumper contacts): 10 A
Derating: Derating (supply voltage): Surrounding air temperatures under laboratory conditions: (-25 … +30 %); for -40 … +55 °C: 24 V (-25 … +20 %); for +55 … +70 °C: 24 V (-25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)
Connection Data
Connection technology: inputs/outputs: 8 x CAGE CLAMP®
Relative humidity (with condensation): Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistance: Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373
Shock resistance: Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373
EMC immunity to interference: Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interference: Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %: 10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %: 25 ppm
Commercial Data
Packaging type: Box
Country of origin Sales Organisation Germany: DE
GTIN: 4050821460398
Customs tariff number Sales Organisation Germany: 85389099990