1. In conjunction with the WAGO I/O System, the KNX IP Controller is used as a user-programmable application controller within KNX IP networks. The controller supports all digital, analog and specialty modules found within the 750/753 Series. The IEC 61131-3 programmable controller is capable of 10/100 Mbit/s data rates. KNX objects of any type (EIS/DPT) can be created using the programming tool. Libraries including pre-made function blocks are readily available on the WAGO Website for programming. The controller supports a maximum of 253 communication objects, as well as 254 group addresses and associations.
2. Combined with the KNX/EIB/TP1 Module, the 750‐889 KNX IP Controller operates as a router on an IP backbone (ETHERNET). No IEC application is required for router functionality.
Approvals
Lloyds Register EMEA, LR, 02/20026 (E6)
Underwriters Laboratories Inc., UL, E198726 Sec.1, UL 121201
RINA Germany GmbH, RINA, ELE066419XG
American Bureau of Shipping, ABS, 19-HG1821926
Det Norske Veritas, Germanischer Lloyd, DNV GL, TAA0000194
UL International Netherlands B.V., UL, E175199 Sec.1, UL 508
Polski Rejestr Statków, PRS, TE/2236/880590/19
National Radio Research Agency, KC, MSIP-REM-W43-PFC750, Article 58-2, Clause 3
Specifications
Notes
Note: The WAGO ETS3/4 plug-in is a component of the WAGO-ETS3 product databank and can be downloaded for free at www.wago.com.
Technical Data
Communication: KNX IP || Modbus (TCP, UDP) || ETHERNET
Programming languages per IEC 61131-3: Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD), Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
Programming environment: WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
Transmission medium (communication/fieldbus): S-UTP; 100 Ω; Cat. 5
Program memory: 1024 kByte
Data memory: 1024 kByte
Non-volatile software memory: 32 kB
Memory for fieldbus input variables (max.): 512 Byte
Memory for fieldbus output variables (max.): 512 Byte
Memory card type: SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO Memory Card)
Memory card slot: Push-push mechanism; Cover lid (sealable)
Number of modules per node (max.): 250
Number of modules without a bus extension (max.): 64
Input and output (fieldbus) process image (max.): 1020 Worte/1020 Worte
Device-specific: Number of group addresses: 254; Number of communication objects: 253
Indicators: LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS/PRG IP, NS/PRG RT) red/green: IP device programming mode, router; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply
Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
Input current (typ.) at nominal load (24 V): 500 mA
Power supply efficiency (typ.) at nominal load (24 V): 90 %
Power consumption (5 V system supply): 450 mA
Total current (system supply): 1700 mA
Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
Current carrying capacity (power jumper contacts): 10 A
Number of outgoing power jumper contacts: 3
Isolation: 500 V system/field
KNX certified: IP Controller: 61/8316/08; IP Router: 61/8317/08
Connection Data
Connection technology: communication/fieldbus: KNX IP: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45
Connection technology: system supply: 2 x CAGE CLAMP®
Connection technology: field supply: 6 x CAGE CLAMP®